6.5.4 Retriggerable Input Mode
The T
IN
Retriggerable Input Mode (TMR bits 5 and 4 are
set to 1) causes T1 to load and start counting on every oc-
currence of a High-to-Low transition on T
IN
(Figure 6-17).
Interrupt request IRQ5 will be generated if the pro-
grammed time interval (determined by T1 prescaler and
counter/timer register initial values) has elapsed since the
last High-to-Low transition on T
IN
. In Single-Pass Mode,
the end-of-count resets the Enable Count bit. Subsequent
T
IN
transitions will not cause T1 to load and start counting
until software sets the Enable Count bit again. In Continu-
ous Mode, counting continues once T1 is triggered until
software resets the Enable Count bit. When enabled, each
High-to-Low T
IN
transition causes T1 to reload and restart
counting. Interrupt request IRQ5 is generated on every
end-of-count.
6.6 CASCADING COUNTER/TIMERS
For some applications, it may be necessary to measure a
time interval greater than a single counter/timer can mea-
sure. In this case, T
IN
and T
OUT
can be used to cascade T0
and T1 as a single unit (Figure 6-18). T0 should be config-
ured to operate in Continuous mode and to drive T
OUT
. T
IN
should be configured as an external clock input to T1 and
wired back to T
OUT
. On every other T0 end-of-count, T
OUT
undergoes a High-to-Low transition that causes T1 to
count.
T1 can operate in either Single-Pass or Continuous mode.
When the T1 end-of-count is reached, interrupt request
IRQ5 is generated. Interrupt requests IRQ2 (T
IN
High-to-
Low transitions) and IRQ4 (T0 end-of-count) are also gen-
erated but are most likely of no importance in this configu-
ration and should be disabled.
Figure 6-18. Cascaded Counter / Timers
OSC
÷
2
÷
4
PRE0
T0
÷
2
PRE1
IRQ
2
P3
1
P3
6
T1
IRQ
4
T
OUT
T
IN
IRQ
5