AC CONTROLLED SOLID STATE RELAY
CLASS 6
AC CONTROLLED INPUT
WITH L.E.D. "ON LAMP"
AC SCR OUTPUT.
High Transient Capability
—Single output
features back to back SCR’s and internally
mounted RC (snubber) network for high dv/dt
applications.
Photo-Isolated, Zero Voltage Switching
—
Optically coupled for 4000 VAC isolation
between input and output and RFI suppression.
IDEC
POTTER &
BRUMFIELD
PART
NUMBERS
CROSS REFERENCE TO:
-
SSR240A25
-
SSR240A50
SSR240A80
-
-
SSR240A25
-
SSR240A50
SSR240A80
OUTPUT CHARACTERISTICS
Rated Load Current (Amps rms)
U/L Incandescent Lamp Ampere Ratings
U/L Motor Load Ampere Ratings
Non-Repetitive Surge Current one Cycle surge (Amps peak)
Maximum rms Overload current for 1 second
Max I
2
T For Fusing ( t= 8-3ms) A
2
sec
Thermal Resistance Junction To Case (T
J
, Max.= 115
0
C)
0
c/w
Minimum Load current, (mA):
2.5 10 25 40 50 75
2.0 8.0 16 30 30 39
1.0 4.5 8.0 14 14 25
100 100 250 350 350 1150
5 24 40 80 100 150
72 72 800 1250 1250 5000
8.5 1.48 1.02 0.63 0.63 0.63
50 50 120 120 120 120
W6110ASX-1
W6125ASX-1
W6140ASX-1
W6150ASX-1
W6175ASX-1
W6202ASX-1
W6210ASX-1
W6225ASX-1
W6240ASX-1
W6250ASX-1
W6275ASX-1
CRYDOM
10 AMPS
25 AMPS
40 AMPS
50 AMPS
75 AMPS
2.5 AMPS
10 AMPS
25 AMPS
40 AMPS
50 AMPS
75 AMPS
MAX.
VOLTAGE
140 VAC
140 VAC
140 VAC
140 VAC
140VAC
280 VAC
280 VAC
280 VAC
280 VAC
280 VAC
280 VAC
0UTPUT
(Over Operating Temperature Range)
NOMINAL
VOLTAGE
RANGE
24-120AC
24-120AC
24-120AC
24-120AC
24-120AC
INPUT
(Over Operating Temperature Range)
MAX.
PULL-IN
VOLTAGE
10 VAC
10 VAC
10 VAC
10 VAC
10 VAC
10 VAC
10 VAC
10 VAC
10 VAC
10 VAC
10 VAC
90 VAC
90 VAC
90 VAC
90 VAC
90 VAC
90 VAC
90 VAC
90 VAC
90 VAC
90 VAC
90 VAC
90 -280 VAC
90 -280 VAC
90 -280 VAC
90 -280 VAC
90 -280 VAC
90 -280 VAC
90 -280 VAC
90 -280 VAC
90 -280 VAC
90 -280 VAC
90 -280 VAC
Part Numbers shown also available thru stocking distribution.
All current ratings are based on use of suitable thermally conductive compound (e.g. silicone grease between the SSR mounting base
and mounting surface of suitable heat sink).
CONTROL
VOLTAGE
RANGE
MIN.
DROPOUT
VOLTAGE
INPUT CHARACTERISTICS
Input Impedance
Response Time
Maximum Rate of Rise of Off State Voltage dv/dt
90 to 280 VAC or 80 to 140 VDC
13K ohms @ 120VAC typical
10 mS Turn ON, 40 mS Turn OFF.
200 500 Volts per microsecond
120 VAC or 240 VAC
RSSAN-10A
RSSAN-25A
RSSAN-40A
RSSAN-50A
RSSAN-75A
-
RSSAN-10A
RSSAN-25A
RSSAN-40A
RSSAN-50A
RSSAN-75A
A1210
A1225
A1240
A1250
A1275
A2402
A2410
A2425
A2440
A2450
A2475
Recognized to Canadian safety
requirements under the Component
Recognition Program of Underwriters
Laboratories Inc.
UL Recognized
File No. E52197
48-240AC
48-240AC
48-240AC
48-240AC
48-240AC
48-240AC
MAX.
CURRENT
RATING
SEE CLASS 6 GENERAL SPECIFICATIONS
PAGE 106
WEBSITE: www.magnecraft.com - EMAIL:info@magnecraft.com - FAX ON DEMAND 1-800/891-2957 - DOCUMENT 100