![](http://datasheet.mmic.net.cn/280000/HP6-X8X4D4D-O_datasheet_16074475/HP6-X8X4D4D-O_2.png)
Nov 7, 2006
Page 2 of 4
www.power-one.com
Multi-Output HP6 Front End
and RACK-HP600 Data Sheet
Input Specifications
Input voltage range:
85 to 264 Vac, 47 to 63 Hz
Power Factor:
0.99 at full load and nominal line
Inrush Current:
40 A peak hot and cold start
Input Protection:
Internal 15 A line fuse
Output Specifications
Output Power:
600 W maximum
Overshoot/Undershoot:
Less than 1% at turn-on or turn-
off. Less than 3% for 50% to 100% load step.
Start-Up Time:
Less than 2 seconds
Efficiency:
78% typical measured at full load, nominal input
Hold-up Time:
20 ms minimum at full load and low line
Single Wire Current Share (V1, V2 and +12V):
10% full
load rating.
Load Regulation:
0.5% with remote sense, 2% without
Line Regulation:
0.1% over entire operating range
Cross Regulation:
Less than 0.5%
Minimum Load:
No minimum load required
Overcurrent Protection:
All outputs set to 115-135% of full
rated load with automatic recovery
Overtemperature Protection:
Automatic shutdown with
auto recovery.
Remote Sense:
Compensates for voltage drop of up to 0.5
V to the load (V1, V2, and +12V). Shorted sense lead
protection.
Overvoltage Protection:
All outputs set at 115%-135% of
nominal. Reset by cycling input power.
Output Noise and Ripple:
PARD: 1% or 50 mV p-p,
whichever is greater, measured at 20 Mhz bandwidth.
Mechanical Specifications
Size:
1.6” H x 5” W x 11.5” D
Input Connector:
Front panel IEC
Output Connector:
FCI power blade
MTBF:
250,000 hours calculated at 25 °C, Bellcore
Standard
Warranty:
Two years from date of shipment, standard
product only.
Specifications are subject to change without prior notice.
Signals and Controls
LED Output Good Indicator:
Front panel green LED indicates
power supply is good; amber indicates fault.
LED AC Good Indicator:
Front panel green LED indicates
Ac input voltage is present and above minimum level.
Output Good Signal*:
TTL compatible signal, normally high.
Goes low when power supply is out of specified range.
Power Fail Signal*:
TTL compatible signal, normally high
(indicating Vin is present and above minimum level).
Enable*:
Normally TTL High, drive low to enable.
*All interface signals are TTL compatible
I
2
C Interface
Event Driven Messages:
Notification of fan speed abnormality
Output voltage under specified ‘good’ range
Output voltage over specified ‘good’ range (software OVP)
Temperature abnormalities
Sensor Device Commands:
Get voltage readings
Get temperature readings
Get fan speed readings
FRU (Field Replaceable Unit) Information Storage:
Manufacturer’s name
Product name
Product part/model number
Product version/revision
Product serial number
Safety & Environmental
Operating Temperature:
0 to 50°C
Storage Temperature:
-40°C to +85°C
Operating Humidity:
Maximum 95% RH non-condensing
Operating Altitude:
10,000 feet
Non-operating Altitude
: 40,000 feet
Temperature Coefficient:
0.02% per °C within rated load
Safety Agency Compliance:
TUV, cTUVus & CB report
EMI:
Meets EN55022, Class B
Harmonic Suppression:
Meets EN6100-3-2
Input Transient Protection:
Electrostatic Discharge: EN61000-4-2, Criteria B
Radiated, Radio-Frequency, Electromagnetic Field:
EN61000-4-3, Criteria A
Electrical Fast Transients/Burst: EN61000-4-4, Criteria B
Voltage Fluctuations and Flickers: EN61000-3-3, Criteria B
Surge Test: EN61000-4-5, Criteria B
Conducted Immunity: EN61000-4-6, Criteria A
Dielectric Withstand:
Input-to-ground: 2200 Vdc
Input-to-output: 4300 Vdc
Output-to-case: 25 Vdc
Ac Leakage Current:
1.2mA maximum at 240 Vac, 50 Hz