Rugged Environment
AC-DC Converters >100 Watt
K Series
Edition 4/4.99
19/28
MELCHER
The Power Partners.
Safety and Installation Instructions
Connector Pin Allocation
The connector pin allocation table defines the electrical
nector. Pin no. 24, the protective earth pin present on all LK
AC-DC converters is leading, ensuring that it makes con-
tact with the female connector first.
Table 12: H15 and H15 S2 Connector pin allocation
Pin
Connector type H15 S2
Connector type H 15
No.
LK 4003
LK 4301, LK 4501, LK 4601
LK 5000
4
Vo1+
Output 1
Vo1+
Output 1
Vo2+
Output 2
6
Vo1+
Vo2+
8
Vo1–
Output 1
Vo1–
Output 1
Vo2–
Output 2
10
Vo1–
Vo2–
12
S+
Sense
S+
Sense
Vo1+
Output 1
14
S–
Sense
S–
Sense
Vo1–
Output 1
16
R 1
Control of
U o1
R 1
Control of
U o1
R 1
Control of
U o1
18
i
Inhibit
i
Inhibit
i
Inhibit
20
D 3
Save data
D
Save data
D
Save data
V 3
ACFAIL
22
T
Current sharing
T
Current sharing
T
Current sharing
24 2
Protective earth
26
N
Neutral
N
Neutral
N
Neutral
28
N
30
P
Phase
P
Phase
P
Phase
32
P
1 Feature R excludes option P and vice versa
2 Leading pin (pregrounding)
3 Option D excludes option V and vice versa
4/6
30/32
Type H15 S2
10001
4
32
Type H15
10002
Fig. 27
View of module's male connectors
Installation Instructions
The K series AC-DC converters are components, intended
exclusively for inclusion within other equipment by an in-
dustrial assembly operation or by professional installers. In-
stallation must strictly follow the national safety regulations
in compliance with the enclosure, mounting, creepage,
clearance, casualty, markings and segregation require-
ments of the end-use application.
Connection to the system shall be made via the female con-
nector H15/H15 S2 (see:
Accessories). Other installation
methods may not meet the safety requirements.
The AC-DC converters are provided with pin no. 24 ( ),
which is reliably connected with their case. For safety rea-
sons it is essential to connect this pin with the protective
earth of the supply system.
An input fuse is built-in in the connection from pins no. 30
and 32 (P~) of the unit. Since this fuse is designed to pro-
tect the unit in case of an overcurrent and does not neces-
sarily cover all customer needs, an external fuse suitable
for the application and in compliance with the local require-
ments might be necessary in the wiring to one or both input
potentials, pins nos. 26 and 28 and/or nos. 30 and 32.
Important: Whenever the inhibit function is not in use, pin
no. 18 (i) should be connected to pin no. 14 (S–/Vo1–) to
enable the output(s).
Do not open the modules, or guarantee will be invali-
dated.