BTE6000 - Series
Precision stainless steel pressure transmitters
January 1998/102
Aubinger Weg 27, 82178 Puchheim, Germany
Phone 0049 - (0) 89 80 08 30, Fax 0049 - (0) 89 8 00 83 33
http://www.sensortechnics.com
Characteristics
Zero pressure offset
BTE6N...
all other
BTE6N...
all other
Full scale span
7
Output impedance
Power consumption (I
L
= 20 mA)
Min.
11.85
3.85
7.9
15.9
Typ.
12.0
4.0
8.0
16.0
0.1
260
Max.
12.15
4.15
8.1
16.1
Unit
mA
mW
4 - 20 mA output, BTE6...
4
Characteristics
Zero pressure offset
BTE6N...
all other
BTE6N...
all other
Full scale span
7
Output impedance
Power consumption (I
L
= 20 mA)
Min.
9.85
-0.15
9.9
19.9
Typ.
10.0
0
10.0
20.0
0.1
260
Max.
10.15
0.15
10.1
20.1
Unit
mA
mW
0 - 20 mA output, BTE6...
5
INDIVIDUAL PERFORMANCE CHARACTERISTICS
1
(unless otherwise noted, V
S
= 15 V, R
L
= 100
, t
amb
= 25°C)
Specification Notes
(for all devices)
1.
2.
3.
4.
5.
6.
7.
8.
The package is a all-sealed housing. IP65 protection is given when the connector is locked with a rubber washer. For proper function the gage port is vented to the atmosphere through
the connector/cable assembly. Thus the cable end must have access to the ambient pressure.
The minimum supply voltage is directly proportional to the load resistance seen by the transmitter. For more details see the oad limitation diagrams.
Proof pressure is the maximum pressure which may be applied without causing damage to the sensing element.
Thermal effects tested and guaranteed from 0°C to 70°C relative to 25°C. All specifications shown are relative to 25°C.
Non-linearity refers to the
B
est
S
traight
L
ine fit measured for offset, full scale span and 1/2 full scale span.
Change after one year or 1 million pressure cycles.
Span is the arithmetic difference in transmitter output signal measured at zero pressure and the maximum operating pressure.
Test are in accordance with EN50082-2, Jan. 93.
ELECTROMAGNETIC CAPABILITY
8
Radiated, radio frequency
electromagnetic field immunity
(RFI)
Electrical fast transient/burst immunity
(EFT)
Electrostatic discharge immunity
(ESD)
Test conditions
IEC801-3:
Grade 3
10V/m, 1MHz to 1000 MHz
unmodulated and 80% modulated
IEC 801-4:
Grade 3
±2 kV
IEC 801-2:
Grade 3
±8 kV, contact discharge
Interference
<1% FSO
<1% FSO
<1% FSO