WESTCODE An IXYS Company
German Standard DIN 110 690V
Data Sheet: 069URxDxxxxB Issue 1
Page 3 of 8
March, 2005
Size
Voltage
Ref:
Current
rating
IN(A)
Pre-arcing
I2t @ 1 ms
I2tp(kA2s)
Total Clearing
I2t @ UN (kA2s)
Watt Losses
0.8IN
IN
Tested
Interrupting
rating
069UR2D0400B
400
15
80
32.5
75
069UR2D0450B
450
20
115
40
80
069UR2D0500B
500
28
145
45
90
069UR2D0550B
550
37
195
47.5
95
069UR2D0630B
630
54
280
52.5
105
069UR2D0700B
700
76
400
55
110
690V
069UR2D0800B
800
115
600
60
120
069UR2D0900B
900
170
900
62.5
125
690V
+6%
069UR2D1000B
1000
240
1250
67.5
135
200kA @660V
2
600V
060UR2D1100B
-
1100
270
1450
82.5
165
200kA @600V
Notes: Minimum operating voltage for integrated trip indicator = 20V
Microswitch Reference : MS 3V 1-5
Size
Voltage
Ref:
Current
rating
IN(A)
Pre-arcing
I2t @ 1 ms
I2tp(kA2s)
Total Clearing
I2t @ UN (kA2s)
Watt Losses
0.8IN
IN
Tested
Interrupting
rating
069UR3D0500B
500
19
100
52.5
105
069UR3D0550B
550
27
140
55
110
069UR3D0630B
630
40
210
60
120
069UR3D0700B
700
55
300
62.5
125
069UR3D0800B
800
95
490
65
130
069UR3D0900B
900
135
700
67.5
135
069UR3D1000B
1000
170
900
77.5
155
690V
069UR3D1100B
1100
240
1260
80
160
069UR3D1250B
1250
350
1850
90
180
690V
+6%
069UR3D1400B
1400
480
2500
100
200
3
600V
060UR3D1600B
-
1600
555
3300
120
240
200kA @660V
170kA @700V
Notes: Minimum operating voltage for integrated trip indicator = 20V
Microswitch Reference : MS 3V 1-5
Electrical Characteristics:
Times vs current characteristics
The following curves indicate the pre-arcing time for each rated current as a function of RMS value of
pre-arcing current I:
-
Tolerances on this current ± 8%
-
Beyond 30 sec or 10 sec, small overloads must be eliminated by another device.
-
Curve CC’ represents the maximum times taken by the associated device to clear small overloads; only its
horizontal line is represented.
Its oblique line must be plotted according to sketch in top right corner:
- The intersection of the fuse and CC’ curves indicates the minimum breaking current Ipm of the fuse.