24
Reversing contactors Type RCI
Features
Compact modular design complete
with heat sink
DIN-rail mountable
Built-in varistor protection
Operational current up to 10 A (AC-3)
Line voltage up 480 V a.c.
Built-in interlock
Universal control voltage
Burst firing (zero cross)
LED status indicator
IP 20 protection
Problem-free specification according
to industry standard
Easy and quick installation
General
Type
RCI 10
Product description
RCI reversing contactors are designed for demanding forward/reverse control of 3-phase AC motors. The zero
cross-switching method ensures very fast and precise motor control and virtually eliminates EMC emission.
The RCI reversing contactor is ideal where fast switching capability and long life are essential.
Typical applications
Conveyors, thread cutting machines, packaging lines and other applications where fast reversing capabilities are needed.
Design standard
IEC/EN 60947-4-2
Approvals
CE, CSA and NRTL/C
Output specifications
Operational current
AC-3 (Motor load)
10 A
AC-4 (Motor load,
inching, jogging)
8 A
Motor size at:
208 - 240 V a.c.
AC-3: 0.1-2.2 kW (0.18-3 HP)
AC-4: 0.1-1.5 kW (0.18-2 HP)
400 - 480 V a.c.
AC-3: 0.1-4 kW (0.18-4 HP)
AC-4: 0.1-3 kW (0.18-4 HP)
Leakage current max.
5 mA
Minimum operational current
50 mA
Semiconductor protection fusing
type 1 coordination
35 A gL/gG
type 2 coordination
450 A
2 S
Thermal specifications
and environment
Power dissipation,
continuous duty
1.2 W/A
Power dissipation,
intermittent duty
1.2 W/A
× duty cycle
Ambient temperature range
-5 to 60 °C
Cooling method
Natural convection
Mounting
Vertical (see also general mounting instructions)
Storage temperature range
-20 to 80 °C
Protection degree/pollution
degree
IP 20/3
Insulation specifications
Rated insulation voltage, Ui
660 V
Rated impulse withstand
voltage, Uimp
4 kV
Installation category
III
Control specifications
Control voltage (+/- 10%)
5 - 24 V d.c . / 24 - 230 V a.c./d.c.
Pick-up voltage
4.25 V d.c. / 20.4 V a.c./d.c.
Drop-out voltage
1.5 V d.c. / 7.2 V a.c./d.c.
Control current/power max.
25 mA at 24 V d.c. / 6 mA / 1.5 VA at 24 V d.c.
Response time max.
1/2 cycle / 1 cycle
Built in switching delay on
forward and reverse, max.
80 m seconds
EMC immunity
Meets requirements of EN 50082-1 and EN 50082-2