18
Motor controllers with Brake, Type MCI 25B
Features
Adjustable acceleration time, 0-10 seconds
Initial torque adjustable from 0-85%,
with or without kick start (break-away)
Adjustable DC injection brake, 0-50 A
d.c.
Fast acting brake mode with automatic
motor field reduction
Automatic stop detection
Universal control voltage 24-480 V
a.c./d.c.
Slow speed function, 7.5% or 10% of
nom. speed
SCR Aux. contacs for external control of
by-pass, I-O and mechanical brake.
Automatic detection of missing phase(s)
Automatic adaptation to 50 or 60 Hz
Unlimited start and stop per hour
IP 20 protection
Compact DIN rail
mountable design
General
Type
MCI 25B
Product description
MCI 25B motor controller with brake is designed for soft starting and braking of 3 phase AC motors. The digital controlled soft
starter features accurate settings and several monitoring functions. Acceleration time and initial torque are along with the braking
torque easily adjusted.
During braking the MCI 25B will apply a DC current to all the windings of the motor, thus providing a powerful brake function.
The automatic stop detection ensures a safe operation. For positioning applications the unique slow speed function can be applied.
Typical applications
The MCI 25B controller is typically applied on demanding braking applications such as saws, cranes, grinding machines,
automatic doors, etc.
Design standard
IEC/EN 60947-4-2
Approvals
CE, CSA and NRTL/C
Output specifications
Operational current AC 3,
AC 53a and AC 58a (motor load)
25 A
Motor size at:
208 - 230 V a.c.
0.7 - 7.5 kW (1-10 HP)
400 - 480 V a.c.
1- 11 kW (1-15 HP)
Leakage current
5 mA a.c. max.
Minimum operational current
50 mA
Overload current profile
X-Tx: 8-3
Overload relay trip class
Class 10
Semiconductor protection fusing
type 1 co-ordination
80 A gL/gG
type 2 co-ordination
6300 A
2S
Thermal specifications
and environment
Power dissipation, continuous duty
2 W/A
Power dissipation, intermittent duty
2 W/A
× duty cycle
Ambient temperature range
-5 to 40 °C
Cooling method
Natural convection
Mounting
Vertical (see also general mounting instructions)
Max. temperature
with limited current
60 °C, see derating for high temperatures in chart below
Storage temperature range
-20 to 80 °C
Protection degree/pollution degree
IP 20/3
Insulation specifications
Rated insulation voltage, Ui
660 V
Rated impulse withstand
voltage, Uimp
4 kV
Installation category
III
Control specifications
Control voltage (+/- 10%)
24 - 480 V a.c./d.c.
Drop-out voltage
5 V a.c./d.c.
Control current/power max.
15 mA/2 VA
Response time max.
70 ms
Ramp-up time
Adjustable 0 - 10 seconds
Brake current
Adjustable 0 - 50 A
Initial torque
Adjustable 0 - 85% of nominal torque, with or without “kick start”
SCR auxialiary contacts
Voltage/current max.
24-480 V a.c./0.5 A (AC-14, AC-15)
Fuse max.
10 A gL/gG, I
2t max 72 A2s
EMC immunity
Meets requirements of EN 50082-1 and EN 50082-2